Appendix
Code table
14−45
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0421*
Free configuration
of analog process
data output words
Output of analog signals to bus
7−64
1 AIF−OUT.W1 8
Operation with process controller (C0238 = 0, 1):
Actual process controller value (PCTRL1−ACT)
Operation without process controller (C0238 =
2):
Output frequency without slip (MCTRL1−NOUT)
2
AIF−OUT.W2 0 Output frequency (MCTRL1−NOUT+SLIP)
3 CAN−OUT1.W1 /
FIF−OUT.W1
255 Not assigned (FIXED−FREE) CAN−OUT1.W1 and FIF−OUT.W1 are
digitally defined in the Lenze setting
and assigned to the 16 bits of the
controller status word 1 (C0417)
Before assigning an analog signal
source (C0421/3 255), first delete
the digital assignment
(C0417/x = 255)! Otherwise, the
output signal would be wrong
4 CAN−OUT1.W2 /
FIF−OUT.W2
255 Not assigned (FIXED−FREE)
5 CAN−OUT1.W3 /
FIF−OUT.W3
255 Not assigned (FIXED−FREE)
6 CAN−OUT1.W4 /
FIF−OUT.W4
255 Not assigned (FIXED−FREE)
7 CAN−OUT2.W1 255 Not assigned (FIXED−FREE)
8 CAN−OUT2.W2 255 Not assigned (FIXED−FREE)
9 CAN−OUT2.W3 255 Not assigned (FIXED−FREE)
10 CAN−OUT2.W4 255 Not assigned (FIXED−FREE)
C0421*
(cont.)
Possible analog signals for C0421 7−64
0 Output frequency (MCTRL1−NOUT+SLIP) 24000 480 Hz
1
Device utilisation (MCTRL1−MOUT) at V/f
characteristic control (C0014 = 2 or 3)
16383 Rated active inverter current
(active current/C0091)
Actual motor torque (MCTRL1−MACT) with vector
control (C0014 = 4) or sensorless torque control
(C0014 = 5)
16383 Rated motor torque
2 Apparent motor current (MCTRL1−IMOT) 16383 Rated inverter current
3 DC−bus voltage (MCTRL1−DCVOLT) 16383 565 VDC at 400 V mains
16383 325 VDC at 230 V mains
4 Motor power 285 Rated motor power
5 Motor voltage (MCTRL1−VOLT) 16383 Rated motor voltage
6 1/output frequency (1/C0050) (MCTRL1−1/NOUT) 195 0.5 C0011
7 Output frequency within adjusted limits
(DCTRL1−C0010...C0011)
24000 480 Hz
0 f C0010
24000 (f C0010)
480Hz
f C0010
8
Operation with process controller (C0238 = 0, 1):
Actual process controller value (PCTRL1−ACT)
24000 480 Hz
Operation without process controller (C0238 =
2):
Output frequency without slip (MCTRL1−NOUT)