EasyManua.ls Logo

Lenze E82ZAFVC010 - Page 61

Lenze E82ZAFVC010
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
Data transfer
Overview of the implemented objects for the function module
9
l
61
EDS82ZAFVCxxx EN 4.0
Instance 4 (COS I/O):
Attribute Service(s) Description Data type Value
1 GET state USINT Status of the object
2 GET instance_type USINT 1
3 GET transportClass_
trigger
BYTE 128/130 (80
hex
/82
hex
)
4 GET produced_
connection_id
UINT Send CAN identifier
5 GET consumed_
connection_id
UINT Reception of CAN identifier
6 GET initial_comm_
characteristics
BYTE 1 (01
hex
)
7 GET produced_
connection_size
UINT Dependent on the number of I/O
data words
8 GET consumed_
connection_size
UINT Dependent on the number of I/O
data words
9 GET / SET expected_
packet_rate
UINT Connection−dependent
10/11 Not used No longer defined
12 GET watchdog_
timeout_action
USINT Defines time−outs
13 GET produced_conne
ction_path_
length
UINT 4
14 GET produced_
connection_path
EPATH [20
hex
, 67
hex
, 24
hex
, 01
hex
]
15 GET consumed_
connection_
path_length
UINT 4
16 GET consumed_
connection_path
EPATH [20
hex
, 68
hex
, 24
hex
, 01
hex
]
17 GET / SET production_
inhibit_time
UINT 0
Services:
Service code Name Description
05
hex
Reset_Request Reset effect:
l Reset of the watchdog timer
l Communication between scanner and slave in
established status.
0E
hex
Get_Attribute_Single Reading an attribute
10
hex
Set_Attribute_Single Writing an attribute

Related product manuals