8400 StateLine C | Operating instructions
Commissioning
Adapting the most important parameters to the drive task
C00034/1
C00026/1
C00027/1
C00010/x
Analog input (AIN1): Configuration
Configuration of the analog input for current or voltage measurement
Selection list (Lenze setting printed in bold) Info
0 -10...+10 V Input signal is the voltage signal -10 V ... +10 V
• -10 V ... +10 V ≡ -100 % ... +100 %
1 0...20 mA Input signal is the current signal 0 mA ... 20 mA
•0mA...20mA ≡ 0%...+100%
2 4...20 mA Input signal is the current signal 4 mA ... 20 mA
•4mA...20mA ≡ 0%...+100%
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Analog input (AIN1): Offset
Setting range (min. value | unit | max. value) Lenze setting
-199.99 % 199.99 0.00 %
Analog input (AIN1): Gain
Setting range (min. value | unit | max. value) Lenze setting
-100.0000 100.0000 1.0000
Analog input (AIN1): characteristic
An individual characteristic according to the right
illustration can be parameterised for the analog input in
order to provide different slopes and a dead band. In this
case the input signal corresponds to the X axis and the
output signal corresponds to the Y axis.
Setting range (min. value | unit | max. value)
0.00 % 199.99
Subcodes Lenze setting Info
C00010/1 0.00 % n AIN1: (+y0) = min
C00010/2 0.00 % o AIN1: (+x0) = Dead band
C00010/3 0.00 % p AIN1: (-y0) = (-min)
C00010/4 0.00 % q AIN1: (-x0) = (-Dead band)
C00010/5 100.00 % r AIN1: (+ymax)
C00010/6 100.00 % s AIN1: (+xmax)
C00010/7 100.00 % t AIN1: (-ymax)
C00010/8 100.00 % u AIN1: (-xmax)
199.99 %