from Firmware V06.00 - DMS 1.1 EN - 11/2011 L 59
8400 StateLine C | Operating instructions
Adapting the application individually
Activating additional functions in the signal flow
8.2 Activating additional functions in the signal flow
The following parameters serve to activate further functions in the main signal flow that
are first deactivated by default:
Parameter Name Info
Application parameters (extended)
C00598/1 Resp. to open circuit AIN1 Response to open circuit at the analog input when
being configured as 4 ... 20 mA current loop.
Lenze setting: "TroubleQuickStop". The drive is braked
to standstill within the deceleration time
parameterised for quick stop independently of the
defined setpoint and can be kept there.
C00950/1 Activation of signal interpolation Signal interpolation and monitoring
(see software manual; FB L_Interpolator_1)
C00950/2 Activation of signal monitoring
C00951 L_Interpolator_1:
No. of interpolation steps
C00952 L_Interpolator_1:
Limit value - error cycles
C00696 L_OffsetGainP_1: Offset Offset and gain
(see software manual; FB L_OffsetGainP_1)
C00670 L_OffsetGainP_1: Gain
C00635 L_NSet_1: nMaxLimit Speed limit values
( 60)
C00636 L_NSet_1: nMinLimit
C0632/1...3 L_NSet_1: Blocking speed 1 ... 3 max Speed blocking zones
( 61)
C0633/1...3 L_NSet_1: Blocking speed 1 ... 3 min
C00134 Ramp rounding - main setpoint Ramp smoothing
( 62)
C00182 S-ramp time PT1
C02830 DIx: Debounce time Debounce and delay times for digital inputs and
outputs
C00423 DOx: Delay times
C00472/3 LS_ParFree_a: Value 3 Torque limitation in motor mode and in generator
mode. Lenze setting: 100 %
The drive cannot output a higher torque in
motor/generator mode than set here.
If V/f characteristic control (VFCplus) is selected,
limitation is indirectly
performed via the Imax
controller.
C00472/4 LS_ParFree_a: Value 4

Table of Contents