8400 StateLine C | Operating instructions
Diagnostics & troubleshooting
Error messages
52 L from Firmware V06.00 - DMS 1.1 EN - 11/2011
 
OC15: Cross current controller limitation Cross current controller limitation is 
active.
 • Observe load requirements.
 • Correct dimensioning or reduce 
setpoint generation dynamics if 
necessary.
 • Check parameter setting of the current 
controller with regard to the motor 
controllers (e.g. reduce Vp).
OC16: Torque controller limitation Actuator limitation according to speed 
controller.
 • Observe load requirements.
 • Correct dimensioning or reduce 
setpoint generation dynamics if 
necessary.
OC17: Clamp sets pulse inhibit Due to a short overcurrent, the inverter 
was switched off for a short time (clamp 
disconnection).
 • Check and, if required, correct 
dimensioning of the load with regard 
to the installed device power.
 • Reduce the dynamics of the setpoint 
change or speed control.
OH1: Heatsink overtemperature The heatsink temperature is higher than 
the fixed limit temperature (90 ° C).
Maybe the ambient temperature of the 
controller is too high or the fan or its 
ventilation slots are dirty.
 • Check control cabinet temperature.
 • Clean filter.
 • Clean controller.
 • If required, clean or replace the fan.
 • Provide for sufficient cooling of the 
device.
OH3: Motor temperature (X106) triggered The motor temperature monitoring 
function at the plug connector X106, 
terminal T1 /T2, has tripped.
Possible causes:
 • The motor is overheated so that the 
thermal contact integrated into the 
motor has been switched.
 • An open circuit or a loose contact at the 
connections mentioned above has 
occurred.
 • Check motor temperature monitoring.
 • Provide for sufficient cooling of the 
motor.
 • Check terminals for open circuit or 
loose contact.
OH4: Heatsink temp. > shutdown temp. -
5°C
The heatsink temperature now only 
differs by 5 °C from the shutdown 
temperature of the motor.
Prevent further heating, i.e. reduce motor 
load or set controller inhibit so that the 
heatsink can cool down again.
OS1: Max. speed limit reached The device has recognised that the 
maximum speed has been reached.
 • Limit setpoint selection to maximum 
values.
 • Adjust set speed limitation (C00909) 
and frequency limitation (C00910) if 
necessary.
OT1: Max. torque reached The device indicates that the maximally 
possible torque at the motor shaft has 
been reached.
 • C00057 displays the current torque.
Reduce motor load.
OT2: Speed controller output limited The output of the speed controller has 
reached the internal limit value. In this 
state, the speed controller is not able 
anymore to correct the system deviation.
 • Only with "Closed loop" operation or 
vector control (SLVC).
 • Observe load requirements.
 • Correct dimensioning or reduce 
setpoint generation dynamics if 
necessary.
OU: DC bus overvoltage The device has detected an overvoltage in 
the DC bus. To protect the device 
hardware, the inverter control is switched 
off.
 • If this error message remains active 
longer than the time set in C00601, a 
"Fault" is tripped.
 • Reduce load in generator mode.
 • Use a brake resistor.
 • Use a regenerative power supply unit.
 • Establish a DC-bus connection.
Error message Cause Remedies