EasyManua.ls Logo

Lenze E84AVSC - Page 72

Lenze E84AVSC
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8400 StateLine C | Operating instructions
Adapting the application individually
Implementing more additional functions in the signal flow
72 L from Firmware V06.00 - DMS 1.1 EN - 11/2011
Parameter
Parameter Name Info/Lenze setting
Process controller
C00242 Operating mode - process controller Selection of the operating mode of the PID process
controller
Basic signal flow
(NSet = main setpoint generator/ramp function generator, MCTRL = motor control, PCTRL = PID process
controller)
0Off
MCTRL setpoint = main setpoint (PID
controller is not in the circuit)
1nNSet + nNSet_PID
MCTRL setpoint =
main setpoint + PID output
PID setpoint = main setpoint
2nSet_PID
MCTRL setpoint = PID output
PID setpoint = main setpoint
3nNSet_PID
MCTRL setpoint = PID output
PID setpoint = main setpoint
4 nNSet + nSet_PID
MCTRL setpoint =
main setpoint + PID output
PID setpoint = own setpoint
5 nNSet || nSet_PID
MCTRL setpoint = main setpoint
PID setpoint = own setpoint
C00222 L_PCTRL_1: Vp 1.0 Gain factor Vp
C00223 L_PCTRL_1: Tn 400 ms Reset time Tn
C00224 L_PCTRL_1: Kd 0.0 Differential component Kd
C00225 L_PCTRL_1: MaxLimit 199.99 % Maximum output value
C00226 L_PCTRL_1: MinLimit -199.99 % Minimum output value
C00227 L_PCTRL_1: Acceleration time 0.010 s Acceleration time for the output value
C00228 L_PCTRL_1: Deceleration time 0.010 s Deceleration time for the output value
C00233 L_PCTRL_1: Root function Use of the root function in the actual value input
0 Root function inactive
The actual value nAct_a remains
unchanged for further processing
1 Root function active
The root is extracted of the actual
value nAct_a for further processing
C00243 L_PCTRL_1: Accel. time influence 5.000 s Acceleration time for showing the PID
output value
C00244 L_PCTRL_1: Deceleration time
influence
5.000 s Deceleration time for masking out the
PID output value
C00247 L_PCTRL_1: ActEqSet window 2.00 % Window for comparison operation
"actual value = setpoint" of the PID
process controller
0&75/
16HW 3&75/
0DLQVHWYDOXH )HHGIRUZDUGFWUOYDO
0&75/
16HW 3&75/
0DLQVHWYDOXH
3,'DFWXDOYDOXH
)HHGIRUZDUGFWUOYDO
0&75/
16HW 3&75/
0DLQVHWYDOXH
3,'DFWXDOYDOXH
0&75/
16HW 3&75/
0DLQVHWYDOXH
3,'DFWXDOYDOXH
0&75/
16HW 3&75/
0DLQVHWYDOXH
3,'DFWXDOYDOXH
)HHGIRUZDUGFWUOYDO
3,'VHWYDOXH
0&75/
16HW 3&75/
0DLQVHWYDOXH
3,'DFWXDOYDOXH
)HHGIRUZDUGFWUOYDO
3,'VHWYDOXH

Table of Contents

Related product manuals