Technical data
Switching frequency reduction
4
39
EDS84DG752 EN 5.0
4.3 Switching frequency reduction
Under certain operating conditions, the maximum output c urrent is limited for all devices:
ƒ When the maximum heatsink temperature is exceeded, the controller switches
from 16 kHz to 8 kHz and from 8 kHz to 4 kHz, irrespective of the switching
frequency mode. This function can be deactivated via C 00144.
If the heatsink temperature increases above 105 °C, the controller is inhibited and the
error message ”OH1: Heatsink overtemperature” is output.
The error response is also triggered when the switching frequency reduction is
deactivated.