5.2.3 Voltage supply
The Communication Unit is supplied with voltage via the AS-i bus cable.
Access to parameters of a device that is disconnected from the mains is not possible.
Permissible voltage (DC) / max. current:
U = 29.5 ... 31.6 V (according to AS-i specification)
•I
max
=120mA
Low-voltage supply via the AS-i-bus cable
In case of low-voltage supply via the AS-i bus cable, communication with the slaves is still possible
if no mains voltage is available.
A previous mains connection (400 V) is not required.
If the mains voltage is not connected, the digital inputs DI1 ... DI4 can be evaluated via slave 2
(FW3.0) or slave 1 and slave 2 (FW2.0).
The AS-i input ports DI0 ... DI3 represent the digital inputs DI1 ... DI4 (see AS-i concept of the
Communication Unit ( 34)). The current status of these inputs can be called.
All digital input and output data that can be selected by the inverter have been deleted or are
invalid.
External sensors are also supplied via the AS-i bus cable.
Note!
An incorrect switch-on sequence of the voltage supply causes an error in the inverter.
First switch on the supply voltage for AS-i, then switch on the mains voltage for the
inverter.
"Inverter Drives 8400 motec" hardware manual
Here you can find detailed information on how to wire the Communication Unit.