Parameter reference
Parameters relevant for AS-i communication
62
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.2 Parameters relevant for AS-i communication
This chapter lists the AS-i parameters of the communication unit in numerically ascending order.
C13200
C13202
Parameter | Name:
C13200 | Active address
Data type: UNSIGNED_8
Index: 11375 = 0x2C6F
Display of the inverter's active address in the AS-i network
Addressing the AS-i slaves
( 27)
Selection list (read only) Info
0 Slave 0(A)
... ...
31 Slave 31(A)
32 Slave 0(B) - invalid
33 Slave 1(B)
... ...
63 Slave 31(B)
64 Slave not active An error message is generated when a slave is
deactivated.
Subcodes Info
C13200/1 Slave 1: Active address
C13200/2 Slave 2: Active address
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13202 | Slave address EPM value
Data type: UNSIGNED_8
Index: 11373 = 0x2C6D
Selection of the inverter's address in the AS-i network
Addressing the AS-i slaves
( 27)
Selection list (Lenze setting printed in bold)
0Slave 0(A)
... ...
31 Slave 31(A)
32 Slave 0(B) - invalid
33 Slave 1(B)
... ...
63 Slave 31(B)
64 Slave not active An error message is generated when a slave is
deactivated.
Subcodes Lenze setting Info
C13202/1 0 Slave 1: Address EPM value
C13202/2 0 Slave 2: Address EPM value
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT