Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019 27
Commissioning
Settings for AS-i communication in the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Settings for AS-i communication in the »Engineer«
6.3.1 Addressing the AS-i slaves
Addressing is usually carried out automatically via the master or an external addressing unit.
The AS-Interface Communication Unit uses two slaves (see AS-i concept of the Communication Unit
( 34)) which must be initialised with unique addresses.
The parameters for addressing the AS-i slaves can be found in the »Engineer« on the "Settings" tab.
Note!
• If the same address is used for slave 1 and slave 2, the address of slave 2 is set to '0'.
• If address '0' is assigned to slave 1 and slave 2, slave 2 is switched "offline" (basic
settings remain intact).
•The setting C13200/x
/ C13202/x = 64 serves to deactivate the slave (not active or
visible in the AS-i network).
Setting / parameters Code
Slave 1: Address EPM value C13202/1
Slave 1: Address EPM value C13202/2
Override slave addresses C13204
Override of the slave addresses during
initialisation
C13205