Diagnostics
LED status displays
54
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10 Diagnostics
For diagnosing troubled AS-i communication, LEDs can be mounted to the Communication Unit.
The LEDs, in conjunction with a transparent cover, can be procured from Lenze.
Moreover, the current bus status can be queried via code C13211
and the internal communication
status can be queried via code C13950
.
10.1 LED status displays
E84DG057
LED statuses for slave 1 and slave 2 Description
Green LEDs Red LEDs
Off Off There is no AS-i voltage.
On Off Everything is alright
AS-i communication is possible.
Off On The slave is switched off; data exchange with the
master is not possible.
On On "No data exchange"
The Data_Exchange_Disable flag is set; data
exchange with the master is not possible.
The IC is waiting for a "Write Parameter Request".
The communication monitoring reports "No data
exchange" or the IC has been reset via "Watchdog
IC Reset".
Blinking (2 Hz) On "No data exchange"
The slave is waiting for address assignment by the
master.
Data exchange with the master is not possible.
Blinking (2 Hz) Blinking (2 Hz) Peripheral error
A signal indicating a peripheral error is pending at
the FID input.
The LEDs are blinking alternately.
On Blinking (2 Hz) Fatal peripheral error with reset
Data sampling pulse = LOW for more than 44 μs