EasyManua.ls Logo

Lenze E84DGFCA Series - Page 38

Lenze E84DGFCA Series
75 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data transfer
Data transmission slave 2 (AS-i profile 7.A.7)
38
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Accessing the parameter bits
Parameter bits P0 ... P3 provide diagnostic information to the master for slave 2. Here, P0 ... P2
define whether a status query of code C00150 or an error/warning diagnostics is returned as slave
response to the master.
The values of P0 ... P3 are transmitted to the master via the "Write_Parameter" command.
Error messages and warnings
Bits Signal / I/O mapping Description
P0 Diagnostic information
(slave master):
4 status bits of the status word
C00150
Error messages / warnings (see
below)
Values P0 - P1 - P2:
0 - 0 - 0: Query C00150/Bits 0 ... 3
0 - 0 - 1: Query C00150/Bits 4 ... 7
0 - 1 - 0: Query C00150/Bits 8 ... 11
0 - 1 - 1: Query C00150/Bits 12 ... 15
1 - 0 - 0: Active error
1 - 0 - 1: Active warning
P1
P2
P3
Note!
No error message / warning is ever provided other than the one with the highest priority.
As long as this error message / warning is pending, no other can be provided.
Values Error message Warning
P0 P1 P2 P3
0 0 0 0 No failure No warning
0001"OC1" - Short circuit "OC5" - Device load warning
0010"OC2" - Ground fault "OC6" - Overload warning
0011 "OH" - High temperature Heat sink temperature high warning
0 1 0 0 "US02" - User error #1 "US01" - User warning #1
0 1 0 1 "OU" - High bus voltage Brake resistor overload
0 1 1 0 "LU" - Low bus voltage error "LU" - Low bus voltage warning
0 1 1 1 "OC6" - Overload error Motor identification active
1 0 0 0 "Su02" - Single phasing "Su02" - Single phasing
1 0 0 1 "US02" - User error #2 "US02" - User warning #2
1 0 1 0 "dbF" - Dynamic brake fault AutoStartLock
1 0 1 1 "PS0x" - EPM failure Motor phase failure
1 1 0 0 "DF0x" - Internal failure AIN current < 4 mA
1101"OH3" - PTC fault Reserved (unused)
1 1 1 0 Drive Unit "offline" Reserved (unused)
1111Other failure Other warnings

Table of Contents