Error messages
Possible causes and remedies
58
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Module internal/watchdog error [0x01bc6010]
Drive PDO communication timeout [0x01bc6011]
Module offline [0x01bc6100]
Module PDO communication timeout [0x01bc6101]
Response (Lenze setting printed in bold) Setting: C01501/1 / C01503 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
Device internal MCU error Switch the voltage supply of the Inverter Drive 8400
motec and the AS-i network off and on again.
If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)
Response (Lenze setting printed in bold) Setting: C01501/2 / C01503 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
Voltage supply of the Inverter Drive 8400 motec
interrupted.
Check wiring and terminals.
Check whether the Inverter Drive 8400 motec is
addressable via the diagnostics interface.
Switch off and on again the voltage supply of the
Inverter Drive 8400 motec.
If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)
Response (Lenze setting printed in bold) Setting: C01501/1 / C01503 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
Device internal MCU error
AS-i voltage supply interrupted.
Connection between the Communication Unit and
the Drive Unit defective.
Check wiring and terminals.
Switch the voltage supply of the AS-i network off and
on again.
If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)
Response (Lenze setting printed in bold) Setting: C01501/1 / C01503 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
AS-i voltage supply interrupted.
Connection between the Communication Unit and
the Drive Unit defective.
Check wiring and terminals.
Switch the voltage supply of the AS-i network off and
on again.
If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)