Error messages
Possible causes and remedies
60
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Slave 1 AS-I ASIC Profile Failure [0x01bc813d]
Slave 2 AS-I ASIC Profile Failure [0x01bc813e]
Response (Lenze setting printed in bold) Setting: C13207/1 / C13208/1 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
The AS-i profile read by slave 1 (via MCU) does not
correspond to the AS-i profile 7.A.5
Module-internal switching error
•AS-i ASIC error
Check voltage supply, wiring and terminals.
Switch the voltage supply of the AS-i network off and
on again.
If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)
Response (Lenze setting printed in bold) Setting: C13207/3 / C13208/3 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
The AS-i profile read by slave 2 (via MCU) does not
correspond to AS-i profile 7.A.7
Module-internal switching error
•AS-i ASIC error
Check voltage supply, wiring and terminals.
Switch the voltage supply of the AS-i network off and
on again.
If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)