Monitoring functions
Configuring monitoring functions
Motor temperature monitoring (OH3, OH7)
9
230
EDBCSXM064 EN 11.0
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
C0583 MONIT OH3 0
Fault response − monitoring of
motor temperature (fixed
temperature threshold).
Detection through KTY thermal
sensor via resolver input X7 or
encoder input X8.
229
0 TRIP
2 Warning
3 Off
C0584 MONIT OH7 2
Fault response − motor
temperature monitoring
Temperature threshold can be
set under C0121.
Detection through KTY thermal
sensor via resolver input X7 or
encoder input X8.
Only effective if OH3 is switched
on under C0583.
229
0 TRIP
2 Warning
3 Off