EasyManua.ls Logo

Lenze ECSEM Series - Page 295

Lenze ECSEM Series
375 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
Code table
12
295
EDBCSXM064 EN 11.0
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
C0349 Status of the DIP switch for CAN
bus interface X4
Read only
1 CAN DIP−SW 0 {1} 63 Node address set on the DIP
switch
2 CAN DIP−SW 0 4 For setting the DIP switches > 4,
the display is set to 0.
C0350 CAN address 32 Node address for CAN bus
interface X4
l This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
( 197)
l After the setting process, a
reset node is required.
l A definite node address must
be assigned to each CAN
node.
197
351
1 {1} 63
C0351 CAN baud rate 0
{4}
Baud rate for CAN bus interface
X4
l The baud rate must be set
identically for all CAN nodes.
l This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
l After the setting process, a
reset node is required.
l When the Lenze setting is
loaded via C0002, C0351 is
set to 0 (500 kbit/s).
197
0 500 kbps
1 250 kbits/sec
2 125 kbit/s
3 50 kbps
4 1000 kbit/s
C0352 CAN mst 0
Boot−up master/slave
configuration for CAN bus
interface X4
203
0 Slave
1 Master boot−up Device is active as CAN boot−up
master.
2 Master node guarding
3 Slave heartbeat producer
4 Slave node guarding
C0353 Source for node address of
CAN_IN/CAN_OUT (CAN bus
interface X4)
201
1 CAN addr sel 0 CAN node address (C0350) Address CAN1_IN/OUT
2 CAN addr sel 0 CAN node address (C0350) Address CAN2_IN/OUT
3 CAN addr sel 0 CAN node address (C0350) Address CAN3_IN/OUT
0 C0350 (auto) Automatically determined by
C0350.
1 C0354 (man.) Determined by C0354.

Table of Contents

Other manuals for Lenze ECSEM Series

Related product manuals