EasyManua.ls Logo

Lenze ECSEM Series - Page 53

Lenze ECSEM Series
375 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
Power terminals
5
53
EDBCSXM064 EN 11.0
Shielded cables
The following factors decisively determine the effect of the shielded cables:
ƒ Good shield connection
Ensure a contact surface as large as possible
ƒ Low shield resistance
Only use shields with tin−plated or nickel−plated copper braids (shields with steel
braids cannot be used).
ƒ High overlap rate of the braid
At least 70 ... 80 % with 90° overlap angle
The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.

Table of Contents

Other manuals for Lenze ECSEM Series

Related product manuals