Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17 49
6 Commissioning
6.5 Establishing an online connection via EtherNet/IP with the Lenze »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.5 Establishing an online connection via EtherNet/IP with the Lenze »Engineer«
[6-2] Example set-up with an Allen Bradley CompactLogix Controller 1769-L32E (scanner)
For an online connection between the »Engineer« and the drive, the drive must have an IP address
(see Setting the IP configuration of the Inverter Drive 8400
( 42)).
Note!
• In order to ensure perfect operation of cyclic EtherNet/IP communication, online
access with the »Engineer« should be executed via an IEEE 802.1Q-capable switch.
• The IEEE 802.1Q-capable switch integrated in the communication module can
manage cyclical EtherNet/IP-communication primarily for normal TCP/IP
communication. In the case of EtherNet/IP, this is done by means of the VLAN
identification in the Ethernet frame (can be set in C13021
).
• If the redundancy protocol DLR (Device Level Ring) is used, the switch also must be
DLR-compliant.