6 Commissioning
6.4 Setting the IP configuration of the Inverter Drive 8400
42
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4 Setting the IP configuration of the Inverter Drive 8400
IP configuration is necessary in order to assign an address to the Inverter Drive 8400 so that
communication between the PC/»Engineer« or the scanner and the drive is possible via EtherNet/
IP. For this purpose, an IP address, subnet mask and gateway address have to be assigned. You can
assign these IP parameters for the Inverter Drive 8400 in the following ways:
• Setting via the EtherNet/IP configurator of the »Engineer«
( 43)
• Setting via codes in the »Engineer«
( 45)
• Setting via a BOOTP/DHCP server
( 47)
• Setting via the TCP/IP Interface Object (0xF5)
( 47)
Note!
• The assignment of invalid combinations of IP address, subnet mask, and gateway
address can have the consequence that no connection to the EtherNet/IP network can
be established.
•Codes C13010
(IP address), C13011 (subnet mask), C13012 (gateway address), and
C13016
(multicast IP address) show the IP parameters currently used.
• In the case of impermissible settings, the error message EtherNet/IP: Invalid IP
parameters [0x01bc6533] ( 99) is output.