10 Monitoring
Fault with regard to EtherNet/IP communication
You can set the reactions of the Inverter Drive 8400 to a fault in EtherNet/IP communication in
»Engineer« by opening the Monitoring tab and making the appropriate settings.
Settings Description
Idle Mode The 32-bit real time header sent by the scanner is evaluated.
Run/Idle Flag (Bit 0) = TRUE:
• The scanner indicates the validity of the I/O data.
Run/Idle Flag (Bit 0) = FALSE:
• The I/O data are invalid and the response parameterised here (C13880/1
)
is executed on the drive.
• The I/O data are processed as set in (C13885
).
Overall Ethernet
Communication Timeout
If there is no reception of explicit or implicit messages after expiry of the
time set in (C13881
) or if access via »Engineer« no longer takes place
after this time, the reaction parameterised here takes place in the drive
(C13880/4
).
Access to the web server is not monitored.
Fault Mode The adapter (communication module) monitors the I/O connection to the
scanner.
If no "implicit message" has been received within the timeout time for
implicit messages parameterised by the scanner, the response
parameterised here (C13880/2
) is executed on the drive.
Overall Ethernet Timeout Time Here, the overall message timeout time (C13881
) is set.
If no message has been received within this time, the response
parameterised in (C13880/4
) is executed.
The following messages are monitored:
• Implicit messages
• Explicit messages
• »Engineer« access via EtherNet/IP
Explicit Msg Timeout If no "explicit message" has been received within the timeout time for
explicit messages parameterised by the scanner, the response
parameterised here (C13880/3
) is executed on the drive.
Clear I/O Data (C13885
), serves to set the I/O data to be processed by the adapter to
maintain internal communication if ...
• the CIP network status (C13862
) of the controlling I/O connection is not
"Connected" or
• an idle event has occurred.