13 Parameter reference
13.1 Parameters of the communication module
120
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13881
C13885
C13899
C13900
C13901
Parameter | Name:
C13881 | Overall Ethernet Timeout Time
Data type: UNSIGNED_16
Index: 10694 = 0x29C6
Setting of the overall monitoring time (see Fault with regard to EtherNet/IP communication ( 88))
A change in the monitoring response becomes immediately effective.
Setting range (min. value | unit | max. value) Lenze setting
500 ms 65535 10000 ms
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear I/O Data
Data type: UNSIGNED_8
Index: 10690 = 0x29C2
Setting which I/O data are to be processed by the adapter to maintain internal communication if ...
the network status of the controlling I/O connection is "Not connected" (see C13862
) or
an idle event has occurred.
Changes in the setting becomes effective immediately.
(See Fault with regard to EtherNet/IP communication
( 88).)
Selection list (Lenze setting printed in bold)
0 Use of last Scanner Output Data
1 Clear Scanner Output Data
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Hostname
Data type: VISIBLE_STRING
Index: 10676 = 0x29B4
Each subcode contains a string with a length of 32 bytes indicating the designation of the EtherNet/IP node.
(Instance attribute 6 (Host Name) in the TCP/IP Interface Object (245 / 0xF5)
( 141))
Subcodes Lenze setting Info
C13899/1 Host name
C13899/2 Host name
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13900 | Firmware Product Type
Data type: VISIBLE_STRING
Index: 10675 = 0x29B3
The code contains a string with a length of 8 bytes. The identification code "E84AYCEO" is output.
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13901 | Firmware Compilation Date
Data type: VISIBLE_STRING
Index: 10674 = 0x29B2
The code contains a string with a length of 20 bytes. The software creation date ("MMM DD YYYY") and time
("hh:mm:ss") are displayed (e.g. "Mar 21 2005 12:31:21").
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT