Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17 99
12 Error messages
12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EtherNet/IP: Invalid IP parameters [0x01bc6533]
EtherNet/IP: Fault Mode [0x01bc8111]
EtherNet/IP: Explicit Message Timeout [0x01bc8112]
EtherNet/IP: Overall Ethernet Timeout [0x01bc8114]
EtherNet/IP: Ethernet cable pulled out [0x01bc8121]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
One or more IP parameters are faulty. Check and correct IP configuration.
Setting the IP configuration of the Inverter Drive 8400
( 42)
Response (Lenze setting printed in bold) Setting: C13880/2
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Connection to scanner has been interrupted.
Controlling I/O connection failed by timeout.
Within the timeout time for implicit messages
parameterised by the scanner, no "implicit messages"
have been received.
Check cables and terminals.
Plug in the network cable into the Ethernet port.
Check Requested Package Interval (RPI) of I/O
connection.
Increase timeout time for implicit messages.
Response (Lenze setting printed in bold) Setting: C13880/3
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Connection to scanner has been interrupted.
Failure of an explicit connection
Within the timeout time for explicit messages
parameterised by the scanner, no "explicit messages"
have been received.
Check cables and terminals.
Plug in the network cable into the Ethernet port.
Check Requested Package Interval (RPI) of the explicit
connection.
Increase timeout time for explicit messages.
Response (Lenze setting printed in bold) Setting: C13880/4
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Failure of »Engineer« communication via Ethernet
When the time set in C13881
has expired, there is no
access via the »Engineer«.
Check cables and terminals.
Plug in the network cable into the Ethernet port.
Increase the overall Ethernet timeout time in C13881
.
Fault with regard to EtherNet/IP communication
( 88)
Response (Lenze setting printed in bold) Setting: not possible
None system fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Network cable has been detached from the Ethernet
terminal.
Network cable (plug) is defective.
Plug the network cable into the Ethernet terminal.
Check the network cable (plug) and replace it if
necessary.