8 I/O data transfer (implicit messages)
8.6 I/O configuration with »RSLogix 5000« version 20 or higher
80
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
 
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 
12. Create an "alias tag".
Example with the assembly object instance 23 (0x17):
For a forward motion of a conveyor, bit ’0’ (Run Fwd) is to be referenced by byte ’0’.
Right-click an assembly tag and select the command "New Tag..." in the context menu.
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
23
(0x17)
0
Net
Ref
NetCtrl Fault
Reset
Run
Rev
Run
Fwd
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Torque Reference (Low Byte)
5
Torque Reference (High Byte)
 Note!
• NetCtrl (Bit 5) and NetRef (Bit 6) have to be set in order that the drive can receive 
start/stop commands and speed/torque command via the network.
• In order to be able to use the torque control of the assembly object distance 23 (0x17), 
the "DriveMode" attribute has to be written by means of explicit message 
transmission.
Write "DriveMode" attribute
 ( 154)