Technical data
3-5
L MA9300PLC EN 1.4
3.4.2 Types 9321 to 9324 with 200 % overcurrent
Type EVS9321-EI EVS9322-EI EVS9323-EI EVS9324-EI
Ratings for operation at a mains: 3 AC / 400V / 50Hz/60Hz
Motor power (4-pole ASM)
P
r
[kW] 0.37 0.75 1.5 3.0
p
(
p
)
P
r
[hp] 0.5 1.0 2.0 4.0
Output power U, V, W (8 kHz) S
r8
[kVA] 1.0 1.7 2.7 4.8
Output current (8 kHz)
2)
I
r8
[A] 1.5 2.5 3.9 7.0
Output current (16 kHz)
2)
I
r16
[A] 1.1 1.8 2.9 5.2
max output current (8 kHz)
1)
I
max8
[A] 3.0 5.0 7.8 14.0
max output current (16 kHz)
1)
I
max16
[A] 2.2 3.6 5.8 10.4
max. standstill current (8 kHz) I
08
[A] 3.0 5.0 7.8 14.0
max. standstill current (16 kHz) I
016
[A] 2.2 3.6 5.8 10.4
Ratings for operation at a mains: 3 AC / 480V / 50Hz/60Hz
Motor power (4-pole ASM)
P
r
[kW] 0.37 0.75 1.5 3.0
p
(
p
)
P
r
[hp] 0.5 1.0 2.0 4.0
Output power U, V, W (8 kHz) S
r8
[kVA] 1.2 2.1 3.2 5.8
Output current (8 kHz)
2)
I
r8
[A] 1.5 2.5 3.9 7.0
Output current (16 kHz)
2)
I
r16
[A] 1.1 1.8 2.9 5.2
max output current (8 kHz)
1)
I
max8
[A] 3.0 5.0 7.8 14.0
max output current (16 kHz)
1)
I
max16
[A] 2.2 3.6 5.8 10.4
max. standstill current (8 kHz) I
08
[A] 3.0 5.0 7.8 14.0
max. standstill current (16 kHz) I
016
[A] 2.2 3.6 5.8 10.4
1)
The currents apply to a periodical load cycle with 10 seconds overcurrent with the current mentio-
ned here and 50 seconds base load with 44 % I
rx
Majority in indiv.
cases
Settings under
code C0022
Thermal
continuous current
Max. current phase Recovery phase
Continuous power I
max
150 % I
rX
100 % I
rX
150 % I
rX
for 60 s 75 % I
rX
for 120 s
Peak power I
max
>
150 % I
rX
70 % I
rX
200 % I
rX
for 10 s 44 % I
rX
r 50 s
2)
This output current Irx applies for a maximum current to be set under C022 which has not excee-
ded 150% of the rated controller current (nameplate).
If the maximum current is higher than this value, the continuous current reduces automatically to
70% of the original value.
All other data: ^
3-4
Tip!
You can change to I
max
> 150% I
rX
only when the controller is inhibited.
Show/Hide Bookmarks