Terminal data
Mains connecon
Inverter i550-C0.25/230-2 i550-C0.37/230-2 i550-C0.55/230-2 i550-C0.75/230-2
Connecon X100
Connecon type pluggable screw terminal
Max. cable cross-secon mm² 2.5 2.5 2.5 2.5
Max. cable cross-secon AWG 12 12 12 12
Stripping length mm 8 8 8 8
Stripping length inch 0.32 0.32 0.32 0.32
Tightening torque Nm 0.5 0.5 0.5 0.5
Tightening torque lb-in 4.4 4.4 4.4 4.4
Required tool 0.5 x 3.0
Mains connecon
Inverter i550-C1.1/230-2 i550-C1.5/230-2 i550-C2.2/230-2 i550-C4.0/230-3
Connecon X100
Connecon type pluggable screw terminal Screw terminal
Max. cable cross-secon mm² 6 6 6 6
Max. cable cross-secon AWG 10 10 10 8
Stripping length mm 8 8 8 9
Stripping length inch 0.32 0.32 0.32 0.35
Tightening torque Nm 0.7 0.7 0.7 0.5
Tightening torque lb-in 6.2 6.2 6.2 4.4
Required tool 0.6 x 3.5
Mains connecon
Inverter i550-C5.5/230-3
Connecon X100
Connecon type Screw terminal
Max. cable cross-secon mm² 6
Max. cable cross-secon AWG 8
Stripping length mm 9
Stripping length inch 0.35
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 0.6 x 3.5
PE connecon
Inverter i550-C0.25/230-2 i550-C0.37/230-2 i550-C0.55/230-2 i550-C0.75/230-2
Connecon PE
Connecon type PE screw
Max. cable cross-secon mm² 6 6 6 6
Max. cable cross-secon AWG 10 10 10 10
Stripping length mm 10 10 10 10
Stripping length inch 0.39 0.39 0.39 0.39
Tightening torque Nm 2 2 2 2
Tightening torque lb-in 18 18 18 18
Required tool Torx 20
Technical data
3-phase mains connecon 230/240 V
Terminal data
108