Motor connecon
Switching in the motor cable
Switching on the motor side of the inverter is permissible:
For safety shutdown (emergency stop).
In case several motors are driven by one inverter (only in V/f operang mode).
Please note the following:
The switching elements on the motor side must be dimensioned for with the
maximum occurring load.
Motor cable lengths
The rated data for the motor cable length must be observed.
Keep the motor cable as short as possible as this has a posive eect on the drive behav-
iour and the EMC.
Several motors connected to an inverter form a group drive.
In case of group drives, the resulng motor cable length l
res
is relevant:
l
res
[m] = (l
1
+ l
2
+ l
3
... l
i
) ∙ √i
l
res
Resulng length of the motor cables
l
x
Length of the single motor cable
i Number of the single motor cables
Shielding
A good shield connecon and short cable lengths reduce possible interferences caused by
problems with the EMC.
Example for preparing the EMC-compliant wiring or the motor cable
l
Fig. 10: Shield connecon
Braid
large surface contacng of the braid
Heat-shrinkable tube
l maximally 500 mm
Informaon on electrical installaon
Motor connecon