Technical data
Standards and operang condions
Conformies/approvals
Conformity
CE 2014/35/EU Low-Voltage Direcve
CE 2014/30/EU EMC Direcve (reference: CE-typical drive system)
EAC TR CU 004/2011 Eurasian conformity: safety of low voltage equipment
EAC TR CU 020/2011 Eurasian conformity: electromagnec compability of technical
means
RoHS 2011/65/EU Restricons for the use of specic hazardous materials in electric
and electronic devices
Approval
UL UL 61800-5-1 for USA and Canada (requirements of the CSA 22.2 No. 274)
UL UL 61800-5-1 File No. E132659
Protecon of persons and device protecon
Enclosure
IP20 EN 60529 Informaon applies to the mounted and ready-for-use state and
not to the wire range of the terminals
NEMA 250 Protecon against contact only according to type 1
Open type Only in UL-approved systems
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulaons and safety instrucons!
Starng current
≤ 3 x rated mains current
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m a.m.s.l.
Overvoltage category II EN 61800-5-1 above 2000 m a.m.s.l.
Control circuit isolaon
Safe mains isolaon by double/reinforced insu-
laon
EN 61800-5-1
Protecve measures against
Short circuit
earth fault Earth fault strength depends on the operang status
Overvoltage
Motor stalling
Motor overtemperature PTC or thermal contact, I²xt monitoring
EMC data
Noise emission
Category C1 EN 61800-3 see rated data
Category C2 EN 61800-3 see rated data
Category C3 EN 61800-3 see rated data
Noise immunity
Meets requirement in compliance with EN 61800-3
Actuaon on public supply systems
Implement measures to limit the radio interfer-
ence to be expected:
The machine or plant manufacturer is responsible for compliance
with the requirements for the machine/plant!
< 1 kW: with mains choke EN 61000-3-2
> 1 kW at mains current ≤ 16 A: without addi-
onal measures
EN 61000-3-2
Mains current > 16 A: with mains choke or
mains lter, when sizing for rated power.
EN 61000-3-12
Technical data
EMC data
73