Periodic inspecons
The correct sequence of the safety−oriented funcons must be checked in periodic inspec-
ons. The risk analysis or applicable regulaons determine the me distances between the
tests.
The inspecon interval should not exceed one year.
Technical data
Rated data
The data applies to products delivered before 1st September 2016.
Safety-related characteriscs according to IEC 61508, Part 1−7 and IEC 62061
Specicaon Value Comment
Safety Integrity Level SIL 2
PFH [1/h] 7.5 E−08 7.5 % of SIL 2
PFD 6.4 E−03 64 % of SIL 2 aer T = 20 years
Proof test interval 20 years Mission me
Safety-related characteriscs according to EN ISO 13849−1
Specicaon Value Comment
Performance Level d
Category 2
MTTF
d
High 530 years
Diagnosc coverage DC Low 60 %
Basics of the safety-related characteriscs
Basics Value Comment
Source of failure rates SN 29500
When no values from the component manufacturers
were available.
Average max. ambient temperature 40 °C
The data applies to products delivered aer 1st September 2016.
Safety-related characteriscs according to EN 61508, Part 1−7 and EN 62061
Specicaon Value Comment
Safety Integrity Level SIL 3
PFH [1/h] 1.71 E−09 1.71 % of SIL 3
PFD
av
(T)
1.49 E−04 14.9 % of SIL 3 aer T = 20 years
Proof test interval 20 years Mission me
Safety-related characteriscs according to EN ISO 13849−1
Specicaon Value Comment
Performance Level e
Category 4
MTTF
d
High 3200 years
Mean diagnosc coverage DC
av
High 99 %
Basics of the safety-related characteriscs
Basics Value Comment
Source of failure rates SN 29500
When no values from the component manufacturers
were available.
Average max. ambient temperature 40 °C
Product extensions
Funconal safety
Technical data
237