RFI lters / Mains lters
Basic informaon on RFI lters, mains lters and EMC: from ^ 246
EMC lters can be used both in the side structure and in the substructure.
Maximum motor cable lengths and FI operaon
Mains connecon 1-phase, 230 V
Inverter i550-C0.25/230-1 i550-C0.55/230-1 i550-C1.1/230-1
i550-C0.37/230-1 i550-C0.75/230-1 i550-C1.5/230-1
i550-C2.2/230-1
Without RFI lter
without EMC cat-
egory
Thermal limitaon
Max. motor cable
length shielded
m 50 50 50
Max. motor cable
length unshielded
m 100 100 200
With integrated RFI lter
Category C1 Max. motor cable
length shielded
m 3 3 3
Category C2 m 15 20 20
Earth-leakage circuit
breaker
mA 30 30 30
RFI lter Low Leakage
Category C1 Max. motor cable
length shielded
m 5 5 5
Earth-leakage circuit
breaker
mA 10 10 10
RFI lter Short Distance
Category C1 Max. motor cable
length shielded
m 25 25 25
Category C2 m 50 50 50
Earth-leakage circuit
breaker
mA 30 30 30
RFI lter Long Distance
Category C1 Max. motor cable
length shielded
m 50 50 50
Category C2 m 50 50 50
Earth-leakage circuit
breaker
mA 300 300 300
Low Leakage
Inverter RFI lter
Order code Dimensions (h x b x t) Weight
mm kg
i550-C0.25/230-1
I0FAE137B100L0000S 226 x 60 x 50 0.85
i550-C0.37/230-1
i550-C0.55/230-1
I0FAE175B100L0000S 276 x 60 x 50 1
i550-C0.75/230-1
i550-C1.1/230-1
I0FAE222B100L0000S 346 x 60 x 50 1.4i550-C1.5/230-1
i550-C2.2/230-1
Technical data
1-phase mains connecon 230/240 V
RFI lters / Mains lters
97