Preparaon
Further data and informaon for mechanical mounng:
4Control cabinet structure ^ 39
4Dimensions ^ 201
The scope of supply of the inverter comprises mounng instrucons. They
describe technical data and informaon on mechanical and electrical installa-
on.
Mounng posion
Vercal alignment - all mains connecons are at the top and the motor connecons at the
boom.
Free spaces
Maintain the specied free spaces above and below to the other installaons.
Mechanical installaon
The mounng locaon and material must ensure a durable mechanical connecon.
Do not mount onto DIN rails!
In case of connuous vibraons or shocks use vibraon dampers.
How to mount the inverters onto the mounng plate.
Requirements:
Mounng plate with conducve surface
Required:
Tool for drilling and thread cung
Screwdriver
Screw and washer assemblies or hexagon socket screws with washers.
1.Prepare mounng plate with corresponding threaded holes.
2.Fit screws and washers (if applicable).
3.Do not yet ghten the screws.
4.Mount the inverter on the prepared mounng plate via keyhole suspension.
5.Only ghten the screws hand-ght.
6.Pre-assemble further units if necessary.
7.Adjust the units.
8.Screw the units onto the mounng plate.
The inverters are mounted on the mounng plate. You can begin with the wiring.
Screw and washer assemblies or hexagon socket screws with washers are recommended..
M5 x ≥ 10 mm for devices up to and including 2.2 kW
M5 x ≥ 12 mm for devices up to and including 11 kW
M6 x ≥ 16 mm for devices up to and including 22 kW
M8 x ≥ 16 mm for devices up to and including 110 kW
Informaon on mechanical installaon