Funconal safety
DANGER!
Improper installaon of the safety engineering system can cause an uncontrolled starng
acon of the drives.
Possible consequences: Death or severe injuries
▶
Safety engineering systems may only be installed and commissioned by qualied and skilled
personnel.
▶
All control components (switches, relays, PLC, ...) must comply with the requirements of the
EN ISO 13849−1 and the EN ISO 13849−2.
▶
Switches, relays with at least IP54 enclosure.
▶
Control cabinet with at least IP54 enclosure.
▶
It is essenal to use shields for the wiring.
▶
It is essenal to use insulated wire end ferrules for wiring.
▶
All safety relevant cables outside the control cabinet must be protected, e.g. by means of a
cable duct
▶
Ensure that no short circuits can occur according to the specicaons of the
EN ISO 13849−2.
▶
All further requirements and measures can be obtained from the EN ISO 13849−1 and the
EN ISO 13849−2.
▶
If an external force acts upon the drive axes, addional brakes are required. Please observe
that hanging loads are subject to the force of gravity!
▶
The user has to ensure that the inverter will only be used in its intended applicaon within
the specied environmental condions. This is the only way to comply with the declared
safety-related characteriscs.
DANGER!
Automac restart if the request of the safety funcon is deacvated.
Possible consequences: Death or severe injuries
▶
You must provide external measures according to EN ISO 13849−1 which ensure that the
drive only restarts aer a conrmaon.
NOTICE
Excessively high humidity or condensaon
Malfuncon or destrucon of the safety component
▶
Only commission the safety component when it has acclimased.
NOTICE
Overvoltage
Destrucon of the safety component
▶
The maximum voltage (maximum rated) at the safety inputs is 30 V DC. The user must make
provisions to avoid that this voltage is exceeded.
Idencaon of the components
Safety components and the respecve terminals are yellow.
Informaon on electrical installaon
Funconal safety
68