PE connecon
Inverter i550-C3.0/400-3 i550-C4.0/400-3 i550-C5.5/400-3 i550-C7.5/400-3
Connecon PE
Connecon type PE screw
Max. cable cross-secon mm² 6 6 6 16
Max. cable cross-secon AWG 10 10 10 6
Stripping length mm 10 10 10 11
Stripping length inch 0.39 0.39 0.39 0.43
Tightening torque Nm 2 2 2 3.4
Tightening torque lb-in 18 18 18 30
Required tool Torx 20 PZ2
PE connecon
Inverter i550-C11/400-3 i550-C15/400-3 i550-C18/400-3 i550-C22/400-3
Connecon PE
Connecon type PE screw
Max. cable cross-secon mm² 16 25 25 25
Max. cable cross-secon AWG 6 2 2 2
Stripping length mm 11 16 16 16
Stripping length inch 0.43 0.63 0.63 0.63
Tightening torque Nm 3.4 4 4 4
Tightening torque lb-in 30 35 35 35
Required tool PZ2
PE connecon
Inverter i550-C30/400-3 i550-C37/400-3 i550-C45/400-3 i550-C55/400-3
Connecon PE
Connecon type PE screw
Max. cable cross-secon mm² 25 25 25 25
Max. cable cross-secon AWG 2 2 2 2
Stripping length mm 16 16 16 16
Stripping length inch 0.63 0.63 0.63 0.63
Tightening torque Nm 4 4 4 4
Tightening torque lb-in 35 35 35 35
Required tool PZ2
PE connecon
Inverter i550-C75/400-3 i550-C90/400-3 i550-C110/400-3
Connecon PE
Connecon type PE screw PE bolt
Max. cable cross-secon mm² 25 150 150
Max. cable cross-secon AWG 2 2 x 2/0 2 x 2/0
Stripping length mm 16 - -
Stripping length inch 0.63 - -
Tightening torque Nm 4 10 10
Tightening torque lb-in 35 89 89
Required tool PZ2 Width across ats 13
Technical data
3-phase mains connecon 400 V "Light Duty"
Terminal data
150