EasyManua.ls Logo

Lenze i550 Series - Page 173

Lenze i550 Series
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mains connecon
Inverter i550-C45/400-3 i550-C55/400-3 i550-C75/400-3 i550-C90/400-3
Connecon X100
Connecon type Screw terminal
Max. cable cross-secon mm² 50 95 95 150
Max. cable cross-secon AWG 1/0 4/0 4/0 2 x 2/0
Stripping length mm 19 22 22 28
Stripping length inch 0.75 0.87 0.87 1.1
Tightening torque Nm 4 10 10 18
Tightening torque lb-in 35 89 89 160
Required tool Hexagon socket 5 Hexagon socket 6 Hexagon socket 8
Mains connecon
Inverter i550-C110/400-3
Connecon X100
Connecon type Screw terminal
Max. cable cross-secon mm² 150
Max. cable cross-secon AWG 2 x 2/0
Stripping length mm 28
Stripping length inch 1.1
Tightening torque Nm 18
Tightening torque lb-in 160
Required tool Hexagon socket 8
PE connecon
Inverter i550-C0.37/400-3 i550-C0.55/400-3 i550-C0.75/400-3 i550-C1.1/400-3
Connecon PE
Connecon type PE screw
Max. cable cross-secon mm² 6 6 6 6
Max. cable cross-secon AWG 10 10 10 10
Stripping length mm 10 10 10 10
Stripping length inch 0.39 0.39 0.39 0.39
Tightening torque Nm 2 2 2 2
Tightening torque lb-in 18 18 18 18
Required tool Torx 20
PE connecon
Inverter i550-C1.5/400-3 i550-C2.2/400-3 i550-C3.0/400-3 i550-C4.0/400-3
Connecon PE
Connecon type PE screw
Max. cable cross-secon mm² 6 6 6 6
Max. cable cross-secon AWG 10 10 10 10
Stripping length mm 10 10 10 10
Stripping length inch 0.39 0.39 0.39 0.39
Tightening torque Nm 2 2 2 2
Tightening torque lb-in 18 18 18 18
Required tool Torx 20
Technical data
3-phase mains connecon 480 V
Terminal data
173

Table of Contents

Other manuals for Lenze i550 Series

Related product manuals