NOTICE
Overvoltage at devices with 230-V mains connecon
An impermissible overvoltage may occur if the central supply of the N conductor is interrup-
ted if the devices are connected to a TN three-phase system.
Possible consequences: Destrucon of the device
▶
Provide for the use of isolang transformers.
NOTICE
The product contains electrostac sensive devices.
Possible consequences: Destrucon of the device
▶
Before working in the connecon area, the sta must ensure to be free of electrostac
charge.
NOTICE
Pluggable terminal strips or plug connecons
Plugging or removing the terminal strips or plug connecons during operaon may cause high
voltages and arcing.
Possible consequences: Damage of the devices
▶
Switch o device.
▶
Only plug or remove the terminal strips or plug connecons in deenergised status.
NOTICE
Use of mains lters and RFI lters in IT systems
Mains lters and RFI lters from Lenze contain components that are interconnected against
PE.
Possible consequences: The lters may be destroyed when an earth fault occurs.
Possible consequences: Monitoring of the IT system may be triggered.
▶
Do not use mains lters and RFI lters from Lenze in IT systems.
▶
Before using the inverter in the IT system, remove the IT screws.
NOTICE
Overvoltage at components
In case of an earth fault in IT systems, intolerable overvoltages may occur in the plant.
Possible consequences: Destrucon of the device.
▶
Before using the inverter in the IT system, the contact screws must be removed.
▶
Posions and number of the contact screws depend on the device.
Ensure a trouble-free operaon:
Carry out the total wiring so that the separaon of the separate potenal areas
is preserved.
Informaon on electrical installaon