Safe mung (MUT)
(From standard device rm
ware V1.3, safety rmware V1.1 with parameter set version V1.1)
The “safe mung
” safety funcon may only be used during commissioning or
maintenance work.
It serves to move the motor even if the inverter is in a safety state.
The safe mung funcon deacvates selected safe inputs and all funcons of the safety bus.
The safe mung funcon can only be acvated via the LSPE (Lenze Safety Parameter Editor).
For this purpose, a special mung password must be entered.
Within a network, the safe mung funcon c
an always only be acvated for one inverter.
The safe mung funcon is maximally acve for 30 minutes. It can be interrupted or stopped
anyme.
Please note the following:
If the sa
fe mung funcon is stopped or interrupted by an error, the inverter
automacally changes to the monitored state.
All safety funcons that have been deacvated before become acve again.
DANGER!
Acvang the sa
fe mung funcon deacvates safety funcons!
This may result in severe injuries or death!
▶
Only authorized personnel is permied to acvate the safe mung funcon.
▶
One input must be parameterized as emergency stop. This input must not be deacvated by
safe mung.
Condions
In order to acv
ate the safe mung funcon, you need the following:
•
A PC with »Easy Starter« (1.16 or higher) or »PLC Designer« with LSPE (Lenze Safety
Parameter Editor).
•
A permanent communicaon link between LSPE and inverter.
If the connecon is interrupted during safe mung, safe mung is aborted immediately
with an error message. The inverter changes to the monitored operaon where all safety
funcons are acve again.
•
A valid parameter set that contains the sengs for safe mung:
•
The sources to be hidden. 0x213A
•
The mung password. 0x213B:001
Acvaon of the funcon
Acvate safe mung
1.Go to the »Easy Starter« and open the Safety parameter list tab.
2.Select safe mung.
3.Enter password.
4.Check informaon in the window and ensure that the correct device has been selected.
The opcal device detecon is acvated automacally. The blinking blue LED indicates the
inverter with acvated safe mung.
5.Start acvates the safe mung funcon.
The safe mung funcon is acve now.
Deacvaon of the funcon
Deacvate safe mung
1.Close deacvates the safe mung funcon for the input.
The safe mung funcon is inacve now.
Product extensions
Funconal sa
fety
Safety funcons