Fusing data
EN 60204-1
Inverter Fuse Circuit breaker Earth-leakage circuit
br
eaker
Characterisc Max. rated
current
Characterisc Max. rated
current
A A
i950-C0.55/400-3 gG/gL or gRL 10 B 10 ≥ 30 mA, type B
i950-C0.75/400-3 gG/gL or gRL 10 B 10 ≥ 30 mA, type B
i950-C2.2/400-3 gG/gL or gRL 16 B 16 ≥ 30 mA, type B
i950-C4.0/400-3 gG/gL or gRL 16 B 16 ≥ 30 mA, type B
i950-C7.5/400-3 gG/gL or gRL 50 B 40 ≥ 300 mA, type B
i950-C11/400-3 gG/gL or gRL 50 B 40 ≥ 300 mA, type B
i950-C15/400-3 gG/gL or gRL 50 B 40 ≥ 300 mA, type B
i950-C22/400-3 gG/gL or gRL 63 B 63 ≥ 300 mA, type B
i950-C30/400-3 gG/gL or gRL 80 B 80 ≥ 300 mA, type B
i950-C45/400-3 gG/gL or gRL 125 B 125 ≥ 300 mA, type B
i950-C55/400-3 gR 160 - - ≥ 300 mA, type B
i950-C75/400-3 gR 160 - - ≥ 300 mA, type B
i950-C90/400-3 gR 300 - - ≥ 300 mA, type B
i950-C110/400-3 gR 300 - - ≥ 300 mA, type B
The c
onnecon data according to UL can be found under:4Connecon according to UL ^ 43
Terminal data
i950-Cxxxx/400-3
Inverter kW 0.55 ... 4.0 7.5 ... 15 22 30 ... 45 55 ... 75 90 ... 110
Connecon Line voltage c
onnecon X100
Connecon type Pluggable screw terminal Screw terminal
Max. cable cross-secon mm² 2.5 16 35 50 95 150
Stripping length mm 8 14 18 19 22 28
Tightening torque Nm 0.5 1.8 3.8 4 10 18
Required tool 0.5 x 3.0 0.8 x 4.0 0.8 x 5.5 Hexagon socket
5
Hexagon socket
6
Hexagon socket
8
i950-Cxxxx/400-3
Inverter kW 0.55 ... 4.0 7.5 ... 15 22 ... 75 90 ... 110 0.55 ... 4.0 7.5 ... 15
Connecon PE c
onnecon Motor connecon X105
Connecon type PE screw PE bolt Pluggable screw terminal
Max. cable cross-secon mm² 6 16 25 150 2.5 16
Stripping length mm 10 11 16 - 8 14
Tightening torque Nm 2 3.4 4 10 0.5 1.8
Required tool Torx 20 PZ2 Width AF 13 0.5 x 3.0 0.8 x 4.0
i950-Cxxxx/400-3
Inverter kW 22 30 ... 45 55 ... 75 90 ... 110
Connecon Motor c
onnecon X105
Connecon type Screw terminal
Max. cable cross-secon mm² 35 50 95 150
Stripping length mm 18 19 22 28
Tightening torque Nm 3.8 4 10 18
Required tool 0.8 x 5.5 Hexagon socket 5 Hexagon socket 6 Hexagon socket 8
The terminal data for the terminal X1 can be found under:4Basic Sa
fety - STO ^ 63
The terminal data for the terminals X82 and X83 can be found under: 4Terminal data ^ 68
Technical data
3-phase mains c
onnecon 400 V
Fusing data