EasyManua.ls Logo

Lenze i950 - RFI Filters; Mains Filters; Short Distance Filter; Long Distance Filter

Lenze i950
184 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RFI lt
ers / Mains lters
Basic informaon on RFI lters, mains lters and EMC: ^ 164
EMC lt
ers can be used both in the side structure and in the substructure.
Short distance lter
Filter type: RFI lter
•
C1 t
o 25 m
•
C2 to 50 m
•
Reduced leakage current, operaon with 30 mA residual current circuit breaker is possible
Inverter Filters
Order code rated current Dimensions (h x w x d) Weight
A mm kg
i950-C0.55/400-3
I0FAE175F100S0000S 3.3 276 x 60 x 50 0.9
i950-C0.75/400-3
i950-C2.2/400-3 I0FAE222F100S0000S 7.8 346 x 60 x 50 1.1
i950-C7.5/400-3
I0FAE311F100S0000S 29 371 x 120 x 60 2.4i950-C11/400-3
i950-C15/400-3
Long Distance lt
er
Filter type up to 15 kW: RFI lter
Filter type from 22 kW: Mains lter (combinaon of RFI lter and mains choke)
•
C1 t
o 50 m
•
C2 to 100 m
•
Operaon with 300 mA residual current circuit breaker
Inverter Filters
Order code rated current Dimensions (h x w x d) Weight
A mm kg
i950-C0.55/400-3
I0FAE175F100D0000S 3.3 276 x 60 x 50 0.9
i950-C0.75/400-3
i950-C2.2/400-3 I0FAE222F100D0000S 7.8
346 x 60 x 50
1.1
i950-C4.0/400-3 I0FAE240F100D0000S 12.5 1.35
i950-C7.5/400-3
I0FAE311F100D0000S 29 371 x 120 x 60 2.1i950-C11/400-3
i950-C15/400-3
i950-C22/400-3 I0FAE322F100D0000S 43 436 x 205 x 90 18.5
i950-C30/400-3 I0FAE330F100D0000S 55
590 x 250 x 105
23
i950-C45/400-3 I0FAE345F100D0001S 100 32
i950-C55/400-3 I0FAE355F100D0001S 120
700 x 250 x 105
36
i950-C75/400-3 I0FAE375F100D0001S 162 41.5
i950-C90/400-3
I0FAE411F100D0001S 240 855 x 250 x 130 63
i950-C110/400-3
Technical data
3-phase mains c
onnecon 480 V
RFI lters / Mains lters