RFI lt
ers / Mains lters
Basic informaon on RFI lters, mains lters and EMC: ^ 164
EMC lt
ers can be used both in the side structure and in the substructure.
Short distance lter
Filter type: RFI lter
•
C1 t
o 25 m
•
C2 to 50 m
•
Reduced leakage current, operaon with 30 mA residual current circuit breaker is possible
Inverter Filters
Order code rated current Dimensions (h x w x d) Weight
A mm kg
i950-C0.55/400-3
I0FAE175F100S0000S 3.3 276 x 60 x 50 0.9
i950-C0.75/400-3
i950-C2.2/400-3 I0FAE222F100S0000S 7.8 346 x 60 x 50 1.1
i950-C7.5/400-3
I0FAE311F100S0000S 29 371 x 120 x 60 2.4i950-C11/400-3
i950-C15/400-3
Long Distance lt
er
Filter type up to 15 kW: RFI lter
Filter type from 22 kW: Mains lter (combinaon of RFI lter and mains choke)
•
C1 t
o 50 m
•
C2 to 100 m
•
Operaon with 300 mA residual current circuit breaker
Inverter Filters
Order code rated current Dimensions (h x w x d) Weight
A mm kg
i950-C0.55/400-3
I0FAE175F100D0000S 3.3 276 x 60 x 50 0.9
i950-C0.75/400-3
i950-C2.2/400-3 I0FAE222F100D0000S 7.8
346 x 60 x 50
1.1
i950-C4.0/400-3 I0FAE240F100D0000S 12.5 1.35
i950-C7.5/400-3
I0FAE311F100D0000S 29 371 x 120 x 60 2.1i950-C11/400-3
i950-C15/400-3
i950-C22/400-3 I0FAE322F100D0000S 43 436 x 205 x 90 18.5
i950-C30/400-3 I0FAE330F100D0000S 55
590 x 250 x 105
23
i950-C45/400-3 I0FAE345F100D0001S 100 32
i950-C55/400-3 I0FAE355F100D0001S 120
700 x 250 x 105
36
i950-C75/400-3 I0FAE375F100D0001S 162 41.5
i950-C90/400-3
I0FAE411F100D0001S 240 855 x 250 x 130 63
i950-C110/400-3
Technical data
3-phase mains c
onnecon 480 V
RFI lters / Mains lters
85