Informaon on electric
al installaon
Important notes
DANGER!
Danger to life due to electric shock!
Dea
th or serious injury
▶
Any work on the inverter must only be carried out in the deenergized state.
▶
Inverter up to 45 kW: Aer switching o the mains voltage, wait for at least 5 min before
you start working.
▶
Inverter above 55 kW: Aer switching o the mains voltage, wait for at least 20 min before
you start working.
DANGER!
Dangerous electrical voltage
The leak
age current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an
error.
▶
Implement the measures requested in EN 61800−5−1 or EN 60204−1. Especially:
▶
Fixed installaon
▶
The PE connecon must comply with the standards (PE conductor diameter ≥ 10 mm
2
or
use a double PE conductor)
NOTICE
No pr
otecon against excessively high mains voltage
The mains input is not fused internally.
Possible consequences: Destrucon of the product in the event of excessively high mains
voltage.
▶
Take note of the maximum permissible mains voltage.
▶
On the mains supply side, use fuses to adequately protect the product against mains
uctuaons and voltage peaks.
DANGER!
Use of the inverter on a phase earthed mains with a rated mains voltage ≥ 400 V
The pr
otecon against accidental contact is not ensured without external measures.
▶
If protecon against accidental contact according to EN 61800-5-1 is required for the control
terminals of the inverters and the connecons of the plugged device modules, ...
▶
an addional basic insulaon has to be provided.
▶
the components to be connected have to come with a second basic insulaon.
Informaon on electric
al installaon
Important notes
40