WARNING!
Dangerous electrical voltage
Err
or on device leads to overvoltage in the system.
▶
For a voltage supply with 24 V DC (± 25 %), use a safely separated power supply unit
according to the applicable SELV/PELV requirements.
▶
All components connected to USB and RJ45 must be electrically isolated from the mains
according to class III.
NOTICE
Overvoltage at devices with 230-V mains c
onnecon
An impermissible overvoltage may occur if the central supply of the N conductor is
interrupted if the devices are connected to a TN three-phase system.
Possible consequences: Destrucon of the device
▶
Provide for the use of isolang transformers.
NOTICE
The product contains electr
ostac sensive devices.
Possible consequences: Destrucon of the device
▶
Before working in the connecon area, the personnel must be free of electrostac charge.
NOTICE
Pluggable terminal strips or plug c
onnecons
Plugging or removing the terminal strips or plug connecons during operaon may cause high
voltages and arcing.
Possible consequences: Damage of the devices
▶
Switch o device.
▶
Only plug or remove the terminal strips or plug connecons in deenergised status.
NOTICE
Use of mains lt
ers and RFI lters in IT systems
Mains lters and RFI lters from Lenze contain components that are interconnected against
PE.
Possible consequences: The lters may be destroyed when an earth fault occurs.
Possible consequences: Monitoring of the IT system may be triggered.
▶
Do not use mains lters and RFI lters from Lenze in IT systems.
▶
Before using the inverter in the IT system, remove the IT screws.
Informaon on electric
al installaon