Inverter i950-C90/400-3 i950-C110/400-3
Rated power kW 90 110
Rated power hp 125 150
Line voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400 V
Rated line current
Without choke A - -
With choke A 168 198
Apparent output power kVA 121 142
Rated output current
2 kHz A 180 212
4 kHz A 180 212
8 kHz A 162 191
16 kHz A 99 106
Power loss
2 kHz W 1855 2177
4 kHz W 1975 2319
8 kHz W 2326 2731
16 kHz W 2326 2731
For controller inhibit W 44 44
Overcurrent cycle 180 s
Max. output current A 270 318
Overload me s 60 60
Recovery me s 120 120
Max. output current during the
r
ecovery me
A 135 159
Overcurrent cycle 15 s
Max. output current A 360 424
Overload me s 3 3
Recovery me s 12 12
Max. output current during the
r
ecovery me
A 135 159
Cyclic line voltage switching Once per minute
Brake chopper
Max. output current A 275 275
Min. brake resistance Ω 2.4 2.4
Max. shielded motor cable length
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 100 100
Without EMC category m 200 200
Weight kg 35.6 35.6
Weight lb 78.5 78.5
Technical data
3-phase mains c
onnecon 400 V
Rated data
75