Commissioning
Configuring the host system (master)
6
37
EDS82ZAFPC010 EN 4.0
Device data base file
The following configurations are saved in the device data base file LENZ00DA.GSE:
Modules in LENZ00DA.GSE
Parameter data
without/with consistency
Process data
without/with consistency
Assigned
I/O memory
Without With Without With
PAR (Cons.) + PZD (n Words)
·
n words 4 + n words
PAR (Cons.) + PZD (n Words Cons.)
·
n words 4 + n words
PAR + PZD (n Words)
·
n words 4 + n words
PZD (n Words) Without parameter data channel n words n words
PZD (n Words Cons.) Without parameter data channel n words n words
n = 1 ... 10
Note!
Device control via FIF status/control word
Device control is only possible if the DRIVECOM status machine (Lenze setting)
is switched off.
ƒ Set C1510 /1 (PIW1) to the value 1":
FIF status word 1 (FIF−STAT1).
ƒ Set C1511 /1 (POW1) to the value 1":
FIF control word 1 (FIF−CTRL1).
ƒ Set C1512 to 65535" to reenable process output words.
For Lenze codes see ( 69)
Tip!
Use overall consistency
ƒ We recommend to use exclusively configurations with consistency for the
parameter data channel to avoid data conflicts between PROFIBUS−DP
master and host CPU.
ƒ Please note that the processing of consistent data varies between hosts.
This must be considered in the PROFIBUS−DP application program.
ƒ Detailed description of consistency: ( 87)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze L-force PROFIBUS-DP and is the answer not in the manual?

Lenze L-force PROFIBUS-DP Specifications

General IconGeneral
BrandLenze
ModelL-force PROFIBUS-DP
CategoryControl Unit
LanguageEnglish

Related product manuals