Commissioning
Configuring the host system (master)
Adapting device controls
6
38
EDS82ZAFPC010 EN 4.0
6.3.1 Adapting device controls
ƒ Lenze device control
Set C1511/1 (POW1) = 1 ð FIF control word 1 (FIF−CTRL1)
Set C1510/1 (PIW1) = 1 ð FIF status word 1 (FIF−STAT1)
ƒ Device control via DRIVECOM
Set C1511/1 (POW1) = 17 ð DRIVECOM control word (DRIVECOM−CTRL)
Set C1510/1 (PIW1) = 18 ð DRIVECOM status word (DRIVECOM−STAT)
For detailed information about the configuration of process data, see chapter "Process
data transfer", 43)
Tip!
Use overall consistency
ƒ Please observe that the processing of consistent data varies between hosts.
This must be taken into account in the PROFIBUS application program.
ƒ A detailed description of consistency can be found in the appendix ( 86)