10 Monitoring
10.3 Settings and displays in the »Engineer«
83
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.3 Settings and displays in the »Engineer«
On the Monitoring tab of the »Engineer«, you can set or display the following parameters:
Parameter Description
Reaction on communication
fault
(C13880/1
)
The response set here takes place if the PROFIBUS station ...
does not receive a message from the master within the watchdog
monitoring time (displayed in C13882/1) if there is an active connection;
recognises that it is not in the "Data_Exchange" status anymore.
Please see also the information on .
Clear process data
(C13885
)
Selection of the process data which the inverter will process in the event of
a PROFIBUS failure in order to maintain internal communication.
The process data sent last by the master can be used or the process data can
be set to zero.
Monitoring time: Data
exchange
(C13881
)
After the monitoring time set here has elapsed, the response set in takes
place for the data exchange.
The value "65535" deactivates the monitoring function.
The monitoring time set here must be smaller than the watchdog
monitoring time .
A change in monitoring is effective immediately.
Permanent interruption of PROFIBUS communication
( 81)
Monitoring time: Watchdog
(C13882/1
)
Display of the watchdog monitoring time determined by the PROFIBUS
master
Monitoring starts with the receipt of the first telegram.
When a value of "0" is displayed, the monitoring function is deactivated.
A change in the watchdog monitoring time in the master is immediately
effective.
Permanent interruption of PROFIBUS communication
( 81)
Set ext. diagnostic bit upon
(C13886
)
Bit-coded selection of the error responses in the standard device causing the
external diagnostic bit ("diag bit") to be set (see PROFIBUS specification; bit 3
of byte 1 of the DP diagnostic messages).
The diagnostic bit is sent to the PROFIBUS master where it is evaluated
separately.
The diagnostic bit is always set when a system error occurs.
The Lenze setting "0" means that the diagnostic bit is not set for the
following error responses.
An advanced diagnostic message is always sent.