13 Parameter reference
13.3 Implemented PROFIdrive objects (DP-V1)
105
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.3 Implemented PROFIdrive objects (DP-V1)
I-918
I-963
I-964
Index | Name:
0x918 | Display of station address
Data type: U16
Display of the station address set
Display area (min. value | unit | max. value)
1 126
; Read access Write access
Index | Name:
0x963 | Baud rate
Data type: U16
Display of the PROFIBUS baud rate
Selection list (read only)
0 9.6 kbps
1 19.2 kbps
2 93.75 kbps
3 187.5 kbps
4 500 kbps
6 1.5 Mbps
7 3 Mbps
8 6 Mbps
9 12 Mbps
10 31.25 kbps
11 45.45 kbps
; Read access Write access
Index | Name:
0x964 | Device identification
Data type: U16
Display of identification data
Subindex Display Info
0x964/0 262 Manufacturer: Lenze
0x964/1 8400 Device type
0x964/2 xxyy Software version, e.g. 0100 (V 01.00)
0x964/3 yyyy Firmware date (year), e.g. 2007
0x964/4 ddmm Firmware date (day/month), e.g. 0506 (5th June)
; Read access Write access