4Technical data
4.1 General data and operating conditions
15
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4 Technical data
4.1 General data and operating conditions
"Inverter Drives 8400" hardware manual
Here you can find the ambient conditions and information on the electromagnetic
compatibility (EMC) which also apply to the communication module.
Area Values
Order designation E84AYCPMV (coated version)
E84AYCPMS (standard version)
Communication profile PROFIBUS DP-V0 (DRIVECOM)
PROFIBUS DP-V1 (PROFIdrive)
Communication medium RS485
Interface 9-pin Sub-D socket
Network topology Line (without repeater)
Tree/line (with repeater)
Bus device type PROFIBUS slave
Number of slaves Max. 31 (without repeater)
Max. 125 (with repeater)
Max. cable length 1200 m (depending on the selected baud rate and the cable type used)
PNO identification number 0x0A89
Baud rate for cable type A (EN 50170) 9.6 kbps ... 12 Mbps (automatic detection)
Conformities, approvals CE
•UL