8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
47
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.3 Free configuration of the port interconnection of process data objects (PDO)
How to freely configure the port interconnection in the »Engineer«:
1. Go to the Process data objects tab and click Go to application.
2. Go to the Ports tab and select the port block "MCI_IN" or "MCI_OUT" via mouse-click.
Activate it by clicking Activate.
3. Click the Edit port ... button.