Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 52
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2 DRIVECOM parameter data channel (DP-V0)
The DRIVECOM parameter data channel (DP-V0) ...
enables parameter setting and diagnosing of the inverter.
provides access to all Lenze parameters (codes).
additionally occupies 4 words (16 bits/word) of the input and output data words in the master.
is identical for both transmission directions.
9.2.1 Telegram structure (overview)
The telegram of the parameter data channel consists of a total of 8 bytes:
The individual bytes are described in detail in the following subchapters.
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
Index
Low byte
Data 4 /
Error 4
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1