EasyManua.ls Logo

Lenze PROFIBUS E84AYCPM - Setting the Station Address

Lenze PROFIBUS E84AYCPM
115 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 32
6 Commissioning
6.3 Setting the station address
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Setting the station address
[6-1] DIP switch
The station addresses must differ from each other if several networked PROFIBUS stations are used.
The station address can be set via DIP switches 1 ... 64 or via the »Engineer« (code C13899
).
The housing labelling indicates the valencies of the individual DIP switches for setting the station
address.
Valid address range: 1 … 126 (max. 126 slave stations)
C13920
: Display of the current address setting of the switches
C13864
: Display of the station address active on the PROFIBUS
E84YCPM001G
The station address can be set via DIP switches 1 ... 64 or via the
»Engineer« (code C13899
).
The unlabelled DIP switch (topmost position) does not have any
function.
Lenze setting: all switches in OFF position
Setting the station address via ...
DIP switch C13899
Condition At least one switch 1…64=ON •Switches 1...64=OFF
All switches 1...64=ON
(invalid value "127")
DIP switch 64 32 16 8 4 2 1
Switch position OFF OFF ON OFF ON ON ON
Value 00
16 0 4 2 1
Station address = sum of the valencies = 16 + 4 + 2 + 1 = 23
DIP switch positions for setting the station address ( 107)
Note!
Switch off the voltage supply of the communication module and then on again in order
to activate changed settings.

Table of Contents

Related product manuals