Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 98
13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13864
C13865
C13866
C13867
Parameter | Name:
C13864 | Active station address
Data type: UNSIGNED_8
Index: 10711
d
= 29D7
h
Display of the active station address
If all DIP switches 1 ... 64 are in the "OFF" position (Lenze setting), the station address set in C13899
becomes active
and is displayed here after switching on.
Setting the station address
( 32)
Display area (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13865 | Display: Most recent PRM data
Data type: OCTET_STRING
Index: 10710
d
= 29D6
h
Display of the last parameter data sent by the PROFIBUS master with the "Set-Prm" telegram (ASCII string with 24
characters)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13866 | Display: Most recent CFG data
Data type: OCTET_STRING
Index: 10709
d
= 29D5
h
Display of the last configuration data sent by the PROFIBUS master with the "Chk-Cfg" telegram (ASCII string with
22 characters)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13867 | Display: Most recent diagnostic data
Data type: OCTET_STRING
Index: 10708
d
= 29D4
h
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
Advanced diagnostic message
( 89)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT