13 Parameter reference
13.1 Parameters of the communication module
97
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13861
C13862
C13863
Parameter | Name:
C13861 | Bus status
Data type: UNSIGNED_16
Index: 10714
d
= 29DA
h
Bit-coded display of the current bus state.
Querying the current bus status
( 88)
Display area (min. value | unit | max. value)
0 65535
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13862 | Bus counter
Data type: UNSIGNED_16
Index: 10713
d
= 29D9
h
When the maximum count value of 65535 is reached, the counter starts again with 0.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13862/1 Data cycles per second
C13862/2 Total data cycles
C13862/3 Total parameterisation events
C13862/4 Total configuration events
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13863 | Baud rate
Data type: UNSIGNED_8
Index: 10712
d
= 29D8
h
Display of the baud rate
Selection list (read only)
0 12.00 Mbps
1 6.00 Mbps
2 3.00 Mbps
3 1.50 Mbps
4 500.00 kbps
5 187.50 kbps
6 93.75 kbps
7 45.45 kbps
8 19.20 kbps
9 9.60 kbps
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT